Home  Product and Services Guide  Stories, articles, and how-to's  Old-House-Friends Forums
Tips & Techniques: Wood Stoves November 22, 2008


How to clean rain lamp...
Member Sign In|Company Sign In





Wood Stoves

MSU Extension
Wood Stoves

What's in this article



more detail


Introduction

Wall Protection

Floor Protection

Stove Pipe

Additional Precautions


Return to the Knowledge Base

 << Previous Page 
Viewing Page 2 of 3
Next Page >> 

Stove Pipe

The stove pipe or chimney connector runs from the stove to the chimney. Many fires associated with wood stoves are caused by unsafe stove pipe installation. A safe installation requires proper material, construction clearances and does provide proper draft. A 24 gauge or thicker metal is recommended; lower gauge numbers indicate thicker metal. This gauge will provide better protection in the event of a chimney fire and will also resist chemical corrosion longer. Most stoves use either a 6 or 8-inch stove pipe. Using stove pipe that is smaller in diameter than the fire box outlet will reduce combustion efficiency and may cause improper draft.

Keep the connector pipe as short as possible. lt should not be longer than 75% of the vertical chimney height above the flue inlet (where the connector pipe enters the chimney). The maximum length is 10 feet. If the pipe runs horizontally, it should have a rise of at least
Causes of creosote formation
Figure 3 - Causes of creosote formation
1/4-inch per linear foot from the elbow or stove outlet to the chimney inlet. Use 45" angles to create an upward slope in the flue connector pipe. Try to have no more than one right angle turn between the stove and chimney. Additional right angle bends can cause soot and creosote to collect in the smoke pipe or chimney, blocking flue gas flow and increasing the danger of a fire.

The connector pipe diameter should be as large as the flue collar (where the connector pipe joins the stove). When joining sections of the pipe, overlap the joints at least 2 inches, with the crimped (male) end pointing down to prevent creosote drip or leak. Many house fires have resulted from stove pipe joints vibrating apart during a chimney fire. Secure each joint with at least 3 sheet metal screws. A fireproof sealant may be used in addition. (See Figure 3)

Clearances from a connector pipe must be 3 times the pipe diameter (a 6-inch pipe needs 18 inches clearance) unless the wall is protected. (See Figure 4) You should not pass a stove pipe through a combustible wall but if a stove pipe must pass through an interior combustible wall in order to hook up with a chimney flue, there are 4 ways to do this safely. (See Figure 5)

Stove pipe clearance with ceiling or wall protection
Figure 4 - Stove pipe clearance with ceiling or wall protection
A - See Table 1 for this distance
B - Minimum distance here is 3 times the diameter of the smoke pipe
1) Use an U.L. "All Fuel" thimble extending through the wall, with a wall hole 4 inches larger than the thimble diameter. This permits the placement of an insulating material such as fiberglass or rock wool between the thimble and the wooden framing of the wall.

2) Use a ventilated thimble that is as least 3 times larger than the stove pipe. For a 6-inch stove pipe, use a thimble that is 18 inches in diameter. This type of thimble is not readily available but can be fabricated by a sheet metal shop. Ventilation through this thimble is an essential aspect of its design; the ventilating holes on either side must not be blocked.

3) Use a fire clay thimble surrounded by 8 inches of brick work or non-combustible material such as rock wool insulation.

4) Use no thimble but remove all combustible materials within 18 inches on all sides of the stove pipe. Material for closing this opening must be non-combustible, with insulating properties.

When the wall is cut between supporting studs for the thimble, inspect the opening to make sure there are no electrical wires or conduit in the space between adjoining wall studs. Heat from the stove pipe may be sufficient to melt the insulation on wire in this space, causing an electrical fire.

Stove pipe should not pass through ceilings, closets, or outside a building. Holes in the ceiling (including hot air registers) permit fires through upper floors. A closet fire could smolder and spread undiscovered.

for safely passing stove pipe through combustable walls
Figure 5 - Thimbles for safely passing stove pipe through combustable walls
Running a stove pipe out a window and up the outside wall of the house is a dangerous practice, because the pipe cools faster than a prefabricated metal chimney and allows a rapid creosote buildup. Wood burners sometimes recommend long spans of single thickness stove pipe as a heating device. This idea had some merit when used with old fashioned inefficient stoves where much of the heat went up the pipe. Today's airtight stoves are more efficient and this practice may cause rapid creosote buildup.

Some stove installations require a damper either built into the stove or in the pipe near the stove to control draft and loss of volatile gases. Check the recommendation of the stove manufacturer.

When connecting the stove pipe to the chimney make sure the fitting is snug at the flue inlet. Use the proper thimble. The pipe must not project into the flue itself, since it would hamper draft.

Long stove pipes and those with restrictions should be cleaned frequently to prevent creosote buildup and possible chimney fires. The entire length of the stove pipe must be easily inspected, firmly fastened at the joints and kept free of all combustible materials. Tap your pipe to check its condition several times during the heating season and before starting the stove each year.

 << Previous Page 
Viewing Page 2 of 3
Next Page >> 



  Ads by Google

  Members:  Sign In  |  Register  |  Benefits  |  Feedback  |  Tell-a-Friend  |  Help
  Companies:  Sign In  |  Account Manager  |  Promote Your Company  |  Register  |  Help Advertise

Copyright ©2008 by Renovators, a TB Systems company. All rights reserved. Privacy policy.